• DocumentCode
    27069
  • Title

    Calculation of townsend second ionization coefficient for photoemission at different humidities

  • Author

    Xu, Mengdi ; Tan, Zhenyu

  • Author_Institution
    School of Electrical Engineering, Shandong University, Jinan 250061, Shandong, P. R. China
  • Volume
    21
  • Issue
    4
  • fYear
    2014
  • fDate
    Aug-14
  • Firstpage
    1764
  • Lastpage
    1767
  • Abstract
    The evaluation of direct current (DC) corona inception voltage in humid air is of importance for high-voltage equipments and high-voltage DC transmission lines, when the occurrence of DC corona in humid air is taken into account. The secondary electrons to sustain a negative DC corona discharge are produced primarily by photoemission from the electrode surface. The process of photoemission in a negative DC corona discharge can be described through the Townsend second ionization coefficient due to photoemission (γp). In this work an approach for the calculations of the Townsend second ionization coefficient γp at different relative humidities has been proposed. Using the presented approach, γp as a function of relative humidity has been calculated and compared with the experiments. The good agreement between the calculated results and the experiments are obtained. The present method is an efficient one for the calculation of γp at different relative humidities, especially for the humidities considered practically, and can be further used for the evaluations of negative DC corona inception electric fields in humid air.
  • Keywords
    Conductors; Copper; Corona; Humidity; Ionization; Photoelectricity; Photonics; Townsend second ionization coefficient; adsorption.; relativehumidity; water molecule; work function;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2014.004101
  • Filename
    6878004