DocumentCode :
2707073
Title :
Water content of XLPE cable components
Author :
Pélissou, S.
Author_Institution :
Hydro-Quebec, Varennes, Que., Canada
fYear :
1994
fDate :
5-8 Jun 1994
Firstpage :
185
Lastpage :
187
Abstract :
This paper presents results of water absorption measurements in several insulation and shield materials taken from unaged medium-voltage cables made by three different manufacturers. Comparisons are made of the water content of two types of water tree retardant XLPE (WTRXLPE) insulation with a conventional XLPE material, and two cleaner conductor and insulation shields with conventional ones. The measurements were performed on cable component chunks after immersion in water at 23, 57 and/or 80°C for various periods of time. The results show that the new cable components absorb much more water by a factor between 2 and 14. Furthermore, the capability of WTRXLPE insulation to retain and/or release water at normal operation temperature (90°C) is also reported: this parameter provides an indirect indication of whether these materials lose their effectiveness with time
Keywords :
XLPE insulation; cable sheathing; moisture; power cable insulation; power cables; trees (electrical); 23 to 90 C; H2O; WTRXLPE insulation; XLPE cable components; XLPE insulation; medium-voltage cables; shield materials; water absorption measurements; water content; water tree retardant insulation; Absorption; Cable insulation; Cable shielding; Cables; Conducting materials; Medium voltage; Pulp manufacturing; Retardants; Time measurement; Trees - insulation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 1994., Conference Record of the 1994 IEEE International Symposium on
Conference_Location :
Pittsburgh, PA
ISSN :
1089-084X
Print_ISBN :
0-7803-1942-7
Type :
conf
DOI :
10.1109/ELINSL.1994.401438
Filename :
401438
Link To Document :