  • Abstract
    It is well known that water-tree is one of the main reasons of XLPE cable insulation aging. With the widespread use of XLPE cables, how to diagnose water-tree aging in insulation becomes more and more important. It has been found that a small DC component will be produced through the insulation of XLPE cables in service. By detection of this DC component, the degree of the cable insulation degradation can be examined, and hot-line diagnosis is realized as well. In this paper, according to a possible model of DC component production, research work of simulating hot-line diagnosis has been conducted with 10 kV XLPE cables in the laboratory. The experimental results indicate that the DC component is in good correspondence with the degradation caused by water trees
  • Keywords
    XLPE insulation; ageing; insulation testing; life testing; power cable insulation; power cable testing; trees (electrical); 10 kV; DC component method; DC component production; cable insulation aging; hot-line XLPE cable diagnosis; insulation degradation; water-tree; Aging; Cable insulation; Cables; Conductors; Copper; Degradation; Laboratories; Leakage current; Production; Trees - insulation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 1994., Conference Record of the 1994 IEEE International Symposium on
  • Conference_Location
    Pittsburgh, PA
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-1942-7
  • Type

    conf

  • DOI
    10.1109/ELINSL.1994.401459
  • Filename
    401459