DocumentCode
2709541
Title
Recognition of defects in high voltage transmission lines using the acoustic signal of corona effect
Author
Tadeusiewicz, Ryszard ; Wszolek, Wieslaw ; Izworski, Andrzej ; Wszolek, Tadeusz
Author_Institution
Univ. of Min. & Metall., Cracow, Poland
Volume
2
fYear
2000
fDate
2000
Firstpage
869
Abstract
The paper deals with the analysis of the possible application of neural networks to the recognition of typical damage of UHV transmission lines. The acoustic signal generated as a result of corona effects is used as a damage symptom, as its intensity is usually increased after damage occurrence or after contamination of the surface of a conductor or an insulator string. The primary problem in the diagnostic process is the distinguishing between signals generated as results of damage and contamination. The problem is not solved by methods based on the RF signal interference or by the classical methods of acoustic signal analysis. The construction and verification of the assumed diagnostic model have been carried out by experimental studies in laboratory conditions, where typical damage and contamination of the transmission line elements have been simulated
Keywords
acoustic signal processing; corona; fault diagnosis; neural nets; power engineering computing; power overhead lines; power transmission faults; UHV transmission lines; acoustic signal; conductor surface contamination; corona effect; experimental studies; fault diagnosis; high voltage transmission lines; insulator string; neural networks; power line defect recognition; Conductors; Corona; Insulation; Neural networks; Radiofrequency interference; Signal generators; Signal processing; Surface contamination; Transmission lines; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Neural Networks for Signal Processing X, 2000. Proceedings of the 2000 IEEE Signal Processing Society Workshop
Conference_Location
Sydney, NSW
ISSN
1089-3555
Print_ISBN
0-7803-6278-0
Type
conf
DOI
10.1109/NNSP.2000.890167
Filename
890167
Link To Document