• DocumentCode
    2711402
  • Title

    Instantaneous Voltage Drop Compensation for UPS System Connected in Parallel with Batteries and Ultracapacitors

  • Author

    Yoon-Ho Kim ; Soo-Hong Kim ; Sung-Chan Rho

  • Author_Institution
    Chung-Ang University, Department of Electrical Engineering, 221 HukSuk-Dong, DongJak-Ku, Seoul, 156-756, Email: yhkim@cau.ac.kr
  • fYear
    2006
  • fDate
    18-22 June 2006
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    This paper proposed an UPS system which is connected in parallel with batteries and ultracapacitors to compensate an instantaneous voltage drop. The topology of the main circuit uses six active switching devices to decrease size and cost of systems. And the proposed UPS system is implemented for 3 [kVA] class. The experimental results shows that the proposed UPS system consist of batteries and ultracapacitors, can compensate a fast instantaneous voltage drop and it has high power factor and low distortion in output voltage and input current.
  • Keywords
    Batteries; Circuits; Costs; Inverters; Power supplies; Rectifiers; Supercapacitors; Switches; Uninterruptible power systems; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics Specialists Conference, 2006. PESC '06. 37th IEEE
  • ISSN
    0275-9306
  • Print_ISBN
    0-7803-9716-9
  • Type

    conf

  • DOI
    10.1109/PESC.2006.1711868
  • Filename
    1711868