DocumentCode
2712613
Title
A New Approach for Calculating Settings of Distance Relays Considering Mutual Coupling Effect
Author
Yang, Zengli ; Duan, Xianzhong
Author_Institution
Huazhong Univ. of Sci. & Technol., Hubei
Volume
3
fYear
2006
fDate
6-8 Sept. 2006
Firstpage
886
Lastpage
889
Abstract
This paper proposes a new systematic approach for calculating settings of all zones of ground distance relays when mutual coupling effect is considered. The proposed zone 1 setting calculation method is based on the apparent impedance seen by the ground distance relays when faults are simulated on the assumed reach of zone 1. Also, it presents a method for calculating zone 2 and zone 3 settings based on the composite current assistance parameter and apparent impedance in the paper. It is shown that the proposed systematic method guarantees the coverage of zone 1 and increases the sensitivity and accuracy of zone 2 and zone 3 settings
Keywords
earthing; fault simulation; relay protection; sensitivity; apparent impedance; fault simulation; ground distance relays; mutual coupling effect; sensitivity; zone setting calculation method; Fault location; Impedance measurement; Large-scale systems; Mutual coupling; Power system faults; Power system measurements; Power system protection; Power system relaying; Protective relaying; Relays; apparent impedance; distance protection; setting calculation; zero sequence current compensation parameter;
fLanguage
English
Publisher
ieee
Conference_Titel
Universities Power Engineering Conference, 2006. UPEC '06. Proceedings of the 41st International
Conference_Location
Newcastle upon Tyne
Print_ISBN
978-186135-342-9
Type
conf
DOI
10.1109/UPEC.2006.367608
Filename
4218816