DocumentCode
2712700
Title
Corona Inception in the Presence of Insulators in a Rod-Plane Gap Under Positive Switching Impulse Voltages
Author
Lazaridis, L.A. ; Mikropoulos, P.N. ; Stassinopoulos, C.A. ; Kerasaridis, C.D. ; Lisaridis, I.G.
Author_Institution
Aristotle Univ. of Thessaloniki
Volume
3
fYear
2006
fDate
6-8 Sept. 2006
Firstpage
912
Lastpage
915
Abstract
Results are presented concerning corona inception in air and in the presence of a porcelain insulator in a non-uniform field under positive switching impulse voltages. It is shown that in the presence of the insulator both first and second coronas start earlier, under lower inception voltages and with smaller associated charges compared to corona inception in air alone. Where the insulator is present, the first and second corona inception voltages and the required voltage increase during dark period increase linearly with the applied voltage. This is not so in the case of corona inception in air alone where the second corona inception voltage was found roughly constant, independent of the applied voltage variations. The apparent first and second corona charges were found to increase with the corresponding inception voltages according to a power and an exponential law respectively
Keywords
air insulation; corona; porcelain insulators; air; corona inception; porcelain insulator; positive switching impulse voltage; rod-plane gap; Breakdown voltage; Charge measurement; Corona; Current measurement; Dielectrics and electrical insulation; Electric variables measurement; Flashover; Porcelain; Surface discharges; Time measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Universities Power Engineering Conference, 2006. UPEC '06. Proceedings of the 41st International
Conference_Location
Newcastle-upon-Tyne
Print_ISBN
978-186135-342-9
Type
conf
DOI
10.1109/UPEC.2006.367612
Filename
4218820
Link To Document