    Comparative study of single-phase earth fault responses of FCC-HVDC and LCC-HVDC

  • Author

    Xu, Jiazhu ; Luo, Longfu ; Bai, Junfeng ; Xiaofang Li ; Li, Yong ; Rehtanz, Christian ; Yang, Dechang ; Häger, Ulf

  • Author_Institution
    Coll. of Electr. & Inf. Eng. Hunan, Univ. Changsha, Changsha, China
  • fYear
    2010
  • fDate
    16-19 May 2010
  • Firstpage
    190
  • Lastpage
    193
  • Abstract
    In order to study the transient response characteristics of Filter Commutated Converter (FCC) under the condition of single-phase earth fault, in the paper, referring to the CIGRE HVDC benchmark testing model (LCC-HVDC), on the basic of non-changing the short circuit ration (SCR) and some parameters, combining the connecting features of FCC, the new testing model based on FCC (FCC-HVDC) is established in the PSCAD/EMTDC; based the two models of LCC-HVDC and FCC-HVDC, the magnetizing and harmonic characteristics are analyzed comparatively under the single-phase earth fault, the results indicated: (1) the magnetizing current of the converter transformer are both a sudden increase and unidirectional magnetization, but the magnetizing characteristics of FCC-HVDC is better than LCC-HVDC; (2) FCC-HVDC still maintains its good harmonic suppression characteristics.
  • Keywords
    Benchmark testing; Circuit faults; Circuit testing; Earth; FCC; Filters; HVDC transmission; Magnetic circuits; Thyristors; Transient response; DC bias; Filter Commutated Converter; harmonic suppression; short circuit ratio; single-phase earth fault; transient response;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Environment and Electrical Engineering (EEEIC), 2010 9th International Conference on
  • Conference_Location
    Prague, Czech Republic
  • Print_ISBN
    978-1-4244-5370-2
  • Electronic_ISBN
    978-1-4244-5371-9
  • Type

    conf

  • DOI
    10.1109/EEEIC.2010.5489971
  • Filename