DocumentCode
2720011
Title
An on-line UPS system with power factor correction and electric isolation using BIFRED converter
Author
Nie, K. ; Bekiarov, S.B. ; Emadi, A.
Author_Institution
Grainger Power Electron. & Motor Drives Lab., Illinois Inst. of Technol., Chicago, IL, USA
Volume
1
fYear
2003
fDate
2-6 Nov. 2003
Firstpage
361
Abstract
This paper presents design consideration and performance analysis of an on-line, low-cost, high performance single-phase Uninterruptible Power Supply (UPS) system based on Boost Integrated Flyback Rectifier/Energy storage DC/DC (BIFRED) converter. The system consists of an isolated AC/DC BIFRED converter, a bi-directional DC/DC converter, and a DC/AC inverter. It has input power factor correction, electric isolation of the input from the output, and control simplicity. Detailed circuit operation, analysis, as well as simulation and experiment results are presented.
Keywords
AC-DC power convertors; DC-AC power convertors; DC-DC power convertors; power factor correction; uninterruptible power supplies; AC-DC BIFRED converter; DC-AC inverter; alternating current; bidirectional DC-DC converter; boost integrated flyback rectifier; direct current; electric isolation; energy storage DC-DC converter; online UPS system; power factor correction; single phase uninterruptible power supply system; Analog-digital conversion; Bidirectional control; Circuits; DC-DC power converters; Energy storage; Inverters; Performance analysis; Power factor correction; Rectifiers; Uninterruptible power systems;
fLanguage
English
Publisher
ieee
Conference_Titel
Industrial Electronics Society, 2003. IECON '03. The 29th Annual Conference of the IEEE
Print_ISBN
0-7803-7906-3
Type
conf
DOI
10.1109/IECON.2003.1280007