Identification of the fault location for three-terminal transmission lines using discrete wavelet transforms
Author
Chiradeja, P. ; Pothisarn, C.
Author_Institution
Fac. of Eng., Srinakharinwirot Univ., Bangkok, Thailand
fYear
2009
fDate
26-30 Oct. 2009
Firstpage
1
Lastpage
4
Abstract
This paper proposes a technique to detect fault locations in a three-bus transmission system using discrete wavelet transform (DWT). The comparison among the first peak time in first scale of each terminal (buses) that can detect fault is performed and the two fastest first peak time obtained from comparison are used as an input data for traveling wave equation later. A comparison of results obtained from three different types of mother wavelet is discussed in order to identify the fault locations with an application of traveling wave theory. It is shown that the db4 mother wavelet produces better results than those from `sym4´ and `coif4´, with a mean error of less than 400 m.
Keywords
discrete wavelet transforms; fault location; power transmission faults; power transmission lines; transmission network calculations; db4 mother wavelet; discrete wavelet transforms; fault location; three-bus transmission system; three-terminal transmission lines; traveling wave equation; Discrete wavelet transforms; EMTP; Fault detection; Fault diagnosis; Fault location; Power system faults; Power transmission lines; Transmission line theory; Transmission lines; Wavelet transforms; ATP/EMTP; Discrete Wavelet Transform; Fault Location; Transmission Line;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission & Distribution Conference & Exposition: Asia and Pacific, 2009
Conference_Location
Seoul
Print_ISBN
978-1-4244-5230-9
Electronic_ISBN
978-1-4244-5230-9
Type
conf
DOI
10.1109/TD-ASIA.2009.5356924
Filename
5356924
Link To Document