Abstract :
This paper describes an investigation of grease degradation of aged GCBs. Risk of depletion on conducting contacts due to grease degradation in particular was identified in field data. In addition, it was found that grease oil evaporation and abrasion dust infiltration were proportional to ages and numbers of operations respectively. It was also found that grease degradation promoted abrasion in silver-plating on sliding contacts, reaching the abnormal abrasion domain for aged equipment, which increased equipment failure risk. Meanwhile, replacement criteria were organized with asset management based on risk evaluation.
Keywords :
abrasion; ageing; circuit breakers; electrical contacts; electrical maintenance; greases; risk analysis; abrasion dust infiltration; aged gas circuit breaker; asset management; equipment replacement criteria; grease degradation; grease oil evaporation; risk evaluation; silver plating; sliding contacts; Aging; Asia; Asset management; Degradation; Equipment failure; Lubrication; Petroleum; Pins; Seals; Shafts; Asset management; GCB; Grease degradation; Replacement criteria; Sliding contacts;