Instantaneous positive-sequence current applied for detecting voltage sag sources
Author :
PolajzÌŒer, BosÌŒtjan ; RÌŒtumberger, Gorazd ; Dolinar, Drago
Author_Institution :
Fac. of Electr. Eng. & Comput. Sci., Univ. of Maribor, Maribor, Slovenia
Volume :
9
Issue :
4
fYear :
2015
fDate :
3 5 2015
Firstpage :
319
Lastpage :
327
Abstract :
This study proposes a method for detecting voltage-sag sources, using only the measurements of line currents. Instantaneous symmetrical components are introduced for accommodating the transient nature of voltage sag events, where a magnitude and phase change in the instantaneous positive-sequence current is used as a criterion. The proposed method is compared with conventional phasor-based methods known from the literature. All the discussed methods for voltage sag source detection, both the already known and the proposed ones, were evaluated by applying extensive simulations, laboratory tests and field testing. When compared with the phasor-based methods, the proposed method showed faster response, a higher degree of confidence and superior effectiveness, especially for transient voltage sag events in networks with distributed generation and active loads.
Keywords :
distributed power generation; electric current measurement; power generation faults; power supply quality; transients; active loads; distributed generation; fleld testing; instantaneous positive sequence current; instantaneous symmetrical components; laboratory tests; line current measurement; phasor-based method; transient voltage sag events; voltage sag source detection;
fLanguage :
English
Journal_Title :
Generation, Transmission & Distribution, IET
Publisher :
iet
ISSN :
1751-8687
Type :
jour
DOI :
10.1049/iet-gtd.2014.0483
Filename :
7062185
Link To Document :
بازگشت