DocumentCode :
272967
Title :
AC-voltage performance of field aged glass insulator strings
Author :
Hyvönen, P. ; Kluss, J.V. ; Taklaja, P.
Author_Institution :
Aalto Univ., Aalto, Finland
fYear :
2014
fDate :
8-11 Sept. 2014
Firstpage :
1
Lastpage :
4
Abstract :
This paper presents the AC-voltage withstand performance of field aged 110kV transmission line glass insulator strings investigated under different environmental conditions. Insulator strings were removed from two 110 kV lines, one located near a coastal area and steel mill industry and the other located inland next to a dump. AC-voltage withstand levels were tested and leakage currents across insulator strings were measured in dry, mist and wet conditions. Results suggest that the polluted insulators from the steel mill should be replaced whereas protective measures need to be applied to the insulators at the dump to mitigate bird-related problems.
Keywords :
electric current measurement; glass; insulators; power transmission lines; power transmission protection; AC-voltage withstand performance; coastal area; dry condition; environmental conditions; field aged transmission line glass insulator strings; leakage current measurement; mist condition; protective measures; steel mill industry; voltage 110 kV; wet condition; Insulators; Pollution measurement; Reliability;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
High Voltage Engineering and Application (ICHVE), 2014 International Conference on
Conference_Location :
Poznan
Type :
conf
DOI :
10.1109/ICHVE.2014.7035428
Filename :
7035428
Link To Document :
بازگشت