Title :
Calculations of generator source short- circuit current according to ANSI/IEEE and IEC standards, with EMTP verifications
Author_Institution :
AMEC, INC., Atlanta, GA, USA
Abstract :
For the interruption of a large generator source-short-circuit current, a current zero may not be obtained at the contact parting time of the circuit breaker. Large generators which have high X/R ratio, and depending upon the relative impedances and time constants the DC component can be higher than the AC decaying component delaying the occurrence of current zero well beyond contact parting time of the circuit breaker. The subject is well addressed in the current literature, though not the calculations of it. This paper presents calculations of a large practical generator using ANSI/IEEE and IEC standards with verifications of results using EMTP. It demonstrates large differences which impact the selection of generator circuit breaker interrupting duties.
Keywords :
ANSI standards; EMTP; IEC standards; circuit breakers; electric generators; short-circuit currents; AC decaying component; ANSI standard; DC component; EMTP simulation; IEC standard; IEEE standard; circuit breaker interrupting duty; generator source short-circuit current calculation; AC generators; Circuit breakers; Circuit faults; DC generators; Delay effects; EMTP; Fault currents; IEC standards; Impedance; Transformers; degree of asymmetry; generator source asymmetrical short-circuit current; lack of current zero at contact separation;
Conference_Titel :
Pulp and Paper Industry Technical Conference, 2009. PPIC '09. Conference Record of 2009 Annual
Conference_Location :
Birmingham, AL
Print_ISBN :
978-1-4244-3464-0
Electronic_ISBN :
0190-2172
DOI :
10.1109/PAPCON.2009.5185412