Abstract
The term `polyphase line protection´ refers to a solid state line protection system in which the measuring units use sequence quantities. Such schemes are designated `polyphase´ since generally each measuring unit can respond to faults of a given type (e.g., phase-to-ground) on all phases or phase-pairs, and some measuring units can respond to different types of faults. Traditionally most GE solid state directional and distance measuring units have employed phase angle comparator circuits. This has been the basic approach used in solid distance relays from the early SLY/SLCG to the latest modular TLS relays. However, these units may also be implemented using an amplitude comparator as well as a phase angle comparator. The use of amplitude comparators is not entirely new in GE designs. They have been used for many years in the SLYP/SLYN and SLYP/SLCN polyphase relay schemes. The operating principles of phase and comparators and the existing amplitude comparators are reviewed followed by an introduction to the new features of the `energy comparators´ to be used in the polyphase line system relay system
Keywords
comparators (circuits); power system protection; relay protection; amplitude comparators; directional relays; distance relays; phase and comparators; polyphase line protection; relay protection; solid state line protection system;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power Protection, 1989., Fourth International Conference on
Conference_Location
Edinburgh
Type
conf
Filename
20640
Link To Document