DocumentCode
2740701
Title
Optimal balancing of large unbalanced loads using shunt compensators
Author
Nikolaenko, V.G.
Author_Institution
Western Power Corp., Perth, WA, Australia
Volume
1
fYear
1998
fDate
14-18 Oct 1998
Firstpage
537
Abstract
Shunt compensators (SCs) with variable susceptances are commonly used for balancing of large unbalanced loads. The control of a balancing SC utilises Steinmetz´s method based on correction of the unbalanced load (UL) to a fully balanced one with unity power factor. This paper presents a model for a balancing SC which extends the SC´s capability to providing any desirable levels of the system balancing and reactive power compensation. The model includes system constraints and provides a full range of possible solutions. Based on this model, the analysis of the SC´s parameters is performed for full and partial balancing with a focus on reducing power ratings of the SC´s primary plant. The calculation technique for optimal parameters of a balancing SC is proposed and illustrated by example
Keywords
compensation; load (electric); power factor; power systems; reactive power; Steinmetz´s method; full balancing; large unbalanced loads; load balancing; optimal balancing; partial balancing; power ratings reduction; reactive power compensation; shunt compensators; unbalanced load correction; unity power factor; variable susceptances; Costs; Electrical equipment industry; Impedance; Industrial power systems; Power system control; Power system modeling; Power systems; Reactive power; Reactive power control; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Harmonics and Quality of Power Proceedings, 1998. Proceedings. 8th International Conference On
Conference_Location
Athens
Print_ISBN
0-7803-5105-3
Type
conf
DOI
10.1109/ICHQP.1998.759966
Filename
759966
Link To Document