• DocumentCode
    2741119
  • Title

    A method for suppressing steady-state operating overvoltages of the half wave-length UHV AC power transmission line

  • Author

    Wang, Ling-tao ; Cui, Xiang

  • Author_Institution
    Key Lab. of High Voltage & EMC Beijing, North China Electic Power Univ., Beijing, China
  • fYear
    2011
  • fDate
    1-4 Nov. 2011
  • Firstpage
    551
  • Lastpage
    554
  • Abstract
    This paper presents a method for suppressing steady-state operating overvoltages at the middle portion of the half wave-length transmission lines based on an unconventional AC transmission system that the half wave-length transmission line is divided into five segments with the different phase spacing and the different split distance. Then an analysis is made of the steady-state operation of a 1000kV-50Hz-3000km transmission system with uniform and nonuniform transmission lines. Simulation results showed that the steady-state operating overvoltages at the middle portion of the power transmission lines can be efficiently suppressed. This method is very convenient to be applied in countries where the transmission lines sites are very distant from the consumption regions.
  • Keywords
    overvoltage protection; power transmission lines; distance 300 km; frequency 50 Hz; half wave-length UHV AC power transmission line; phase spacing; split distance; steady-state operating overvoltages; voltage 1000 kV; Conductors; Distributed parameter circuits; Power transmission lines; Reactive power; Steady-state; Surges; UHV; half wave-length AC power transmission; overvoltage; power factor; steady-state operating;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Lightning (APL), 2011 7th Asia-Pacific International Conference on
  • Conference_Location
    Chengdu
  • Print_ISBN
    978-1-4577-1467-2
  • Type

    conf

  • DOI
    10.1109/APL.2011.6110187
  • Filename