DocumentCode :
2743581
Title :
Calibration of an instrument current transformer at a ratio of 20 kA/5 A
Author :
Draxler, Karel ; Styblíková, Renata ; Kucera, Jan ; Rada, Vlastimil
Author_Institution :
Fac. of Electr. Eng., CTU in Prague, Prague, Czech Republic
fYear :
2012
fDate :
1-6 July 2012
Firstpage :
14
Lastpage :
15
Abstract :
This paper presents two methods for determining the ratio error and phase displacement of an instrument current transformer (ICT) with transformation ratio 20 kA/5 A. In the first case, the primary conductor passed by a current 20 kA placed in the centre of the toroid is replaced by a current loop with 10 turns placed in the centre of the toroid. In the second case, the conductor is replaced by 10 turns uniformly distributed along the circumference of the toroid. The primary current 2 kA is measured in both cases using a toroidal current comparator, and the secondary current difference is evaluated by means of an ICT error measurement system.
Keywords :
calibration; conductors (electric); current comparators; current transformers; electric current measurement; instrument transformers; measurement errors; transformer windings; ICT error measurement system; calibration; conductor; current 2 kA; current 20 kA; current loop; instrument current transformer; phase displacement; ratio error; toroidal current comparator; Calibration; Current measurement; Current transformers; Measurement uncertainty; Standards; Uncertainty; Windings; Instrument current transformer (ICT); current comparator; current loop; error evaluation system; phase displacement; ratio error;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Precision Electromagnetic Measurements (CPEM), 2012 Conference on
Conference_Location :
Washington, DC
ISSN :
0589-1485
Print_ISBN :
978-1-4673-0439-9
Type :
conf
DOI :
10.1109/CPEM.2012.6250635
Filename :
6250635
Link To Document :
بازگشت