  • Abstract
    The Standards and Calibration Laboratory (SCL) of Hong Kong has developed a primary standard of power based on sampling principle. The primary standard is used to provide calibration service for precision power meters. The measurement uncertainty is 55 × 10-6 for voltage from 24 to 480 V and current from 0.005 to 160 A and power factor from unity to 0 leading or lagging.
  • Keywords
    calibration; measurement standards; power meters; voltage measurement; Hong Kong; SCL; Standards and Calibration Laboratory; current 0.005 A to 160 A; measurement uncertainty; power factor; precision power meter; primary power standard; sampling principle; voltage 24 V to 480 V; Current measurement; Current transformers; Measurement uncertainty; Power measurement; Reactive power; Standards; Voltage measurement; Precision power measurements (active, reactive, apparent); impedance; phase angle; power factor; sampling principle;