DocumentCode
2744943
Title
Q-hour meter performance under unbalanced voltage supply
Author
Baghzouz, Y. ; Cox, M.D.
Author_Institution
Dept. of Electr. & Comput. Eng., Nevada Univ., Las Vegas, NV, USA
Volume
2
fYear
1998
fDate
14-18 Oct 1998
Firstpage
1131
Abstract
This article investigates the error associated with reactive power and power factor when calculated from a set of watt-hour and Q-hour meters in a circuit where an unbalanced sinusoidal supply feeds a linear balanced load. An analytical expression of the error is derived in terms of the level of voltage unbalance. It is found that this method under-estimates reactive power thus leading to higher power factor at all times but the error is well within meter tolerance for typical levels of unbalance
Keywords
power factor measurement; reactive power; watthour meters; Q-hour meter performance; Q-hour meters; calculation error; linear balanced load; power factor measurement; reactive power measurement; unbalanced sinusoidal supply; unbalanced voltage supply; watt-hour meters; Capacitors; Circuits; Energy measurement; Feeds; Impedance; Industrial power systems; Power measurement; Reactive power; Voltage measurement; Watthour meters;
fLanguage
English
Publisher
ieee
Conference_Titel
Harmonics and Quality of Power Proceedings, 1998. Proceedings. 8th International Conference On
Conference_Location
Athens
Print_ISBN
0-7803-5105-3
Type
conf
DOI
10.1109/ICHQP.1998.760197
Filename
760197
Link To Document