DocumentCode :
2747357
Title :
Study and development of a measurement set-up for high impulse currents
Author :
Istrate, D. ; Blanc, I. ; Fortune, D.
Author_Institution :
Lab. Nat. de Metrol. et d´´Essai (LNE, Trappes, France
fYear :
2012
fDate :
1-6 July 2012
Firstpage :
224
Lastpage :
225
Abstract :
The understanding of high current events such as short circuit transients and impulse currents is important for the management of power quality. The work carried out and presented in this paper is focused on the characterization of commercial current transducers for on-site grade and traceable measurements of 8/20 μs (rise/fall time) impulse currents up to 60 kA peak value with a target uncertainty of 0.1 % for the complete measurement system. The investigation method consists in using two current transducers (Pearson and Rogowski coils) that will detect simultaneously the same impulse current.
Keywords :
electric current measurement; power supply quality; short-circuit currents; transducers; Pearson coil; Rogowski coil; commercial current transducers; current 60 kA; current transducers; high impulse currents; impulse currents; measurement set-up; power quality management; short circuit transients; Calibration; Coils; Current measurement; Measurement uncertainty; Time measurement; Transducers; Uncertainty; Impulse current; Pearson current monitor; Rogowski coil; comparison technique; measurement dynamics;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Precision Electromagnetic Measurements (CPEM), 2012 Conference on
Conference_Location :
Washington, DC
ISSN :
0589-1485
Print_ISBN :
978-1-4673-0439-9
Type :
conf
DOI :
10.1109/CPEM.2012.6250883
Filename :
6250883
Link To Document :
بازگشت