• DocumentCode
    2749751
  • Title

    Electromagnetic transient interference measurement system of UHV Fixed Series Capacitors at high potential and EMI characterization

  • Author

    Qiyan Ma ; Xiang Cui ; Rong Hu ; Weidong Zhang ; Huiwen Liu ; Xiong Zhan ; Jinsong Yu ; Hongtao Liu

  • Author_Institution
    State Key Lab. of Alternate Electr. Power Syst., North China Electr. Power Univ., Beijing, China
  • fYear
    2012
  • fDate
    17-21 Sept. 2012
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Switch operation and bypass gap sparkover in Ultrahigh Voltage (UHV) Fixed Series Capacitors (FSC) produce fast on-platform transient overvoltage in primary side and couple into the protection and control system of secondary side. To understand the electromagnetic interference (EMI) characteristics of UHV FSC in both primary and secondary side, we focus on high-potential and on-platform primary-side overvoltage and secondary-side disturbance measurement on a life-size experimental platform. Firstly, we set up a Series Capacitors Electromagnetic Transient Interference Measurement System (SCEMS) and demonstrated its efficiency by a series of laboratory performance test. Secondly, by isolating disconnect switch of the UHV FSC experimental platform, the necessity and effectiveness of shielding for on-platform SCEMS was verified, and primary-side overvoltage and secondary-side disturbance were obtained. Lastly, characterization of EMI data in amplitude, time and frequency domain was analyzed, and statistical distribution of P-P (peak to peak) value described. The measurement system, SCEMS, and the high-potential measurement technique in UHV FSC, where applicable, are to extend to Series Capacitors (SC) at different voltage levels, regardless of fixed capacitors or controllable capacitors. Experimental data is suitable to use by designers and engineers in EMC solutions, insulation cooperation, and equipment arrangement optimization.
  • Keywords
    capacitors; electromagnetic interference; frequency-domain analysis; measurement systems; optimisation; overvoltage protection; sparks; statistical distributions; switchgear; time-domain analysis; EMC solutions; P-P statistical distribution; UHV FSC experimental platform; UHV fixed series capacitors; amplitude domain analysis; bypass gap sparkover; controllable capacitors; disconnect switch isolation; electromagnetic fast on-platform transient overvoltage; equipment arrangement optimization; frequency domain analysis; high-potential measurement technique; high-potential on-platform primary-side overvoltage; laboratory performance test; life-size experimental platform; on-platform SCEMS; peak-to-peak statistical distribution; primary-side overvoltage; secondary side control system; secondary side protection; secondary-side disturbance measurement; series capacitors electromagnetic transient interference measurement system; switch operation; time domain analysis; ultra-high voltage fixed series capacitors; voltage levels; Current measurement; Interference; Power capacitors; Transient analysis; Voltage control; Voltage measurement; Electromagnetic Interference (EMI); Fixed Series Capacitors (FSC); High-potential measurement; Series Capacitors Electromagnetic Transient Interference Measurement System (SCEMS); Ultra-high Voltage (UHV);
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electromagnetic Compatibility (EMC EUROPE), 2012 International Symposium on
  • Conference_Location
    Rome
  • ISSN
    2325-0356
  • Print_ISBN
    978-1-4673-0718-5
  • Type

    conf

  • DOI
    10.1109/EMCEurope.2012.6396744