DocumentCode :
275292
Title :
Isolated power systems: problems of waveform distortion due to thyristor converter loading
Author :
Graham, J.J. ; Halsall, C.L. ; McKay, I.S.
Author_Institution :
Paisley Coll. of Technol., UK
fYear :
1990
fDate :
17-19 Jul 1990
Firstpage :
327
Lastpage :
330
Abstract :
The system described enables efficient reduction of the line unbalance due to a three phase AC/AC converter feeding an unbalanced load. The cancellation of the inverse component of the line currents fundamentals is chosen as a balancing criterion. It induces a perfect power flow balancing among the three lines because power only deals with fundamentals quantities. Just a little unbalance remains about the other harmonics involving a very small difference between the RMS values of the line currents. The process is rather universal and enables these advantages to be obtained for other power electronics unbalanced circuits
Keywords :
power convertors; power systems; thyristor applications; line unbalance; power electronics; power flow balancing; three phase AC/AC converter; thyristor converter loading; unbalanced circuits; unbalanced load; waveform distortion;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Power Electronics and Variable-Speed Drives, 1991., Fourth International Conference on
Conference_Location :
London
Type :
conf
Filename :
114663
Link To Document :
بازگشت