Effect of transient model of arrester on transient recovery voltage
Author :
Vahidi, B. ; Goodarzi, E. ; Hosseinian, S.H. ; Tavakoli, M. R Bank
Author_Institution :
Amirkabir Univ. of Technol., Tehran
fYear :
2007
fDate :
Oct. 30 2007-Nov. 2 2007
Firstpage :
1
Lastpage :
3
Abstract :
Circuit breakers can fail to interrupt fault current when the power system has transient recovery voltage (TRV) characteristics that exceed the rating of circuit breaker. TRV is the voltage across the opening contacts of a fault interrupting circuit breaker immediately after the arc is extinguished. The actual shape of the transient is determined by the connected lumped and distributed inductive and capacitive parameters defined by the bus equipment connected. Most of researcher has worked on TRV but not so much work is done on rate of rise of recovery voltage (RRRV). In the present paper fast transient model of arrester is used to simulate and analyze the TRV and RRRV by using MATLAB-SIMULINK software. The results of this simulation show the benefit of fast transient model of arrester for this kind of study.
Keywords :
arresters; circuit breakers; fault currents; power system simulation; power system transients; MATLAB-SIMULINK software; arrester transient model; circuit breakers; fast transient model; fault current; rate of rise of recovery voltage; transient recovery voltage; Arresters; Circuit breakers; Circuit faults; Fault currents; Mathematical model; Power system faults; Power system modeling; Power system transients; Transient analysis; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
TENCON 2007 - 2007 IEEE Region 10 Conference
Conference_Location :
Taipei
Print_ISBN :
978-1-4244-1272-3
Electronic_ISBN :
978-1-4244-1272-3
Type :
conf
DOI :
10.1109/TENCON.2007.4429038
Filename :
4429038
Link To Document :
بازگشت