DocumentCode :
2757248
Title :
Transformer-less series voltage injection for reactive power compensation of line-commutated HVDC
Author :
Jafar, Milimonfared ; Molinas, Marta
Author_Institution :
Norwegian Univ. of Sci. & Technol., Trondheim, Norway
fYear :
2012
fDate :
4-6 Sept. 2012
Abstract :
A transformer-less series-voltage injection strategy has been suggested for reactive power compensation of line-commutated HVDC systems. It has been shown that series voltages injected at appropriate times using transformer-less full-bridge arrangement can force early commutation on the rectifier side thereby bringing the phase angle between the voltage and current to a smaller value than the conventional 15° value. Simulation results indicate reactive power compensation as well as reduction in consumption by the HVDC terminal. This can lead to smaller HVDC terminal size due to elimination of shunt-capacitor-bank requirement. The results indicate that the requirement for capacitors in the suggested topology is much smaller than fixed series capacitor.
Keywords :
HVDC power transmission; rectifiers; fixed series capacitor; line-commutated HVDC systems; phase angle; reactive power compensation; rectifier side; shunt-capacitor-bank requirement elimination; terminal size; transformer-less full-bridge arrangement; transformer-less series-voltage injection strategy; Capacitors; HVDC transmission; Reactive power; Rectifiers; Switches; Thyristors; Voltage control; HVDC transmission control; Power electronics; Reactive power control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics and Motion Control Conference (EPE/PEMC), 2012 15th International
Conference_Location :
Novi Sad
Print_ISBN :
978-1-4673-1970-6
Electronic_ISBN :
978-1-4673-1971-3
Type :
conf
DOI :
10.1109/EPEPEMC.2012.6397319
Filename :
6397319
Link To Document :
بازگشت