DocumentCode
2757767
Title
An improved voltage phasor estimation technique to minimize the impact of CCVT transients in distance protection
Author
Pajuelo, E. ; Ramakrishna, G. ; Sachdev, M.S.
Author_Institution
Power Syst. Res. Group, Saskatchewan Univ., Saskatoon, Sask.
fYear
2005
fDate
1-4 May 2005
Firstpage
454
Lastpage
457
Abstract
This paper describes the impact of the transient response of coupling capacitor voltage transformers (CCVTs) on the performance of distance relays. Several factors that affect the frequency and time responses of CCVTs are considered. The effect of the transient response on phasor estimation is illustrated. A new least squares phasor estimation technique, which uses the knowledge of the frequency of the CCVT transients, is presented. A sample case, taken from a set of studies, is included to demonstrate the performance of the proposed approach
Keywords
least squares approximations; phase estimation; potential transformers; power transformer protection; CCVT transients; coupling capacitor voltage transformers; distance protection; frequency response; least squares phasor estimation technique; time response; voltage phasor estimation technique; Frequency; Inductance; Power system faults; Power system protection; Power system relaying; Power system transients; Protective relaying; Transient response; Transmission line measurements; Voltage transformers;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical and Computer Engineering, 2005. Canadian Conference on
Conference_Location
Saskatoon, Sask.
ISSN
0840-7789
Print_ISBN
0-7803-8885-2
Type
conf
DOI
10.1109/CCECE.2005.1556969
Filename
1556969
Link To Document