DocumentCode :
2757767
Title :
An improved voltage phasor estimation technique to minimize the impact of CCVT transients in distance protection
Author :
Pajuelo, E. ; Ramakrishna, G. ; Sachdev, M.S.
Author_Institution :
Power Syst. Res. Group, Saskatchewan Univ., Saskatoon, Sask.
fYear :
2005
fDate :
1-4 May 2005
Firstpage :
454
Lastpage :
457
Abstract :
This paper describes the impact of the transient response of coupling capacitor voltage transformers (CCVTs) on the performance of distance relays. Several factors that affect the frequency and time responses of CCVTs are considered. The effect of the transient response on phasor estimation is illustrated. A new least squares phasor estimation technique, which uses the knowledge of the frequency of the CCVT transients, is presented. A sample case, taken from a set of studies, is included to demonstrate the performance of the proposed approach
Keywords :
least squares approximations; phase estimation; potential transformers; power transformer protection; CCVT transients; coupling capacitor voltage transformers; distance protection; frequency response; least squares phasor estimation technique; time response; voltage phasor estimation technique; Frequency; Inductance; Power system faults; Power system protection; Power system relaying; Power system transients; Protective relaying; Transient response; Transmission line measurements; Voltage transformers;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical and Computer Engineering, 2005. Canadian Conference on
Conference_Location :
Saskatoon, Sask.
ISSN :
0840-7789
Print_ISBN :
0-7803-8885-2
Type :
conf
DOI :
10.1109/CCECE.2005.1556969
Filename :
1556969
Link To Document :
بازگشت