  • Title

    An improved voltage phasor estimation technique to minimize the impact of CCVT transients in distance protection

  • Author

    Pajuelo, E. ; Ramakrishna, G. ; Sachdev, M.S.

  • Author_Institution
    Power Syst. Res. Group, Saskatchewan Univ., Saskatoon, Sask.
  • fYear
    2005
  • fDate
    1-4 May 2005
  • Firstpage
    454
  • Lastpage
    457
  • Abstract
    This paper describes the impact of the transient response of coupling capacitor voltage transformers (CCVTs) on the performance of distance relays. Several factors that affect the frequency and time responses of CCVTs are considered. The effect of the transient response on phasor estimation is illustrated. A new least squares phasor estimation technique, which uses the knowledge of the frequency of the CCVT transients, is presented. A sample case, taken from a set of studies, is included to demonstrate the performance of the proposed approach
  • Keywords
    least squares approximations; phase estimation; potential transformers; power transformer protection; CCVT transients; coupling capacitor voltage transformers; distance protection; frequency response; least squares phasor estimation technique; time response; voltage phasor estimation technique; Frequency; Inductance; Power system faults; Power system protection; Power system relaying; Power system transients; Protective relaying; Transient response; Transmission line measurements; Voltage transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical and Computer Engineering, 2005. Canadian Conference on
  • Conference_Location
    Saskatoon, Sask.
  • ISSN
    0840-7789
  • Print_ISBN
    0-7803-8885-2
  • Type

    conf

  • DOI
    10.1109/CCECE.2005.1556969
  • Filename
    1556969