• DocumentCode
    2757927
  • Title

    Failure of service aged 230 kV current transformers

  • Author

    McDermid, W. ; Black, T.

  • Author_Institution
    Manitoba Hydro, Winnipeg, MB, Canada
  • fYear
    2012
  • fDate
    10-13 June 2012
  • Firstpage
    235
  • Lastpage
    236
  • Abstract
    As of the spring of 2008 Manitoba Hydro had in service up to 39 current transformers rated 230 kV from a particular supplier. These had been manufactured in 1969, 1971 and 1975. Three failed explosively beginning in the summer of 2008. Dissolved gas-in-oil analysis revealed others with significant fault gas. As of the end of 2011 all remaining 230 kV current transformers of this type had been removed from service. The paper reviews the design, transport, service conditions and age which may have contributed to the high failure rate.
  • Keywords
    chemical analysis; current transformers; failure analysis; power transformer insulation; transformer oil; dissolved gas-in-oil analysis; failure analysis; fault gas; high failure rate; oil filled current transformers; service aged current transformer failure; voltage 230 kV; Circuit faults; Current transformers; Hair; Hydrogen; Nitrogen; Partial discharges; Windings; failure analysis; oil filled current transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation (ISEI), Conference Record of the 2012 IEEE International Symposium on
  • Conference_Location
    San Juan, PR
  • ISSN
    1089-084X
  • Print_ISBN
    978-1-4673-0488-7
  • Electronic_ISBN
    1089-084X
  • Type

    conf

  • DOI
    10.1109/ELINSL.2012.6251464
  • Filename
    6251464