Analysis of AC and DC flat transmission lines lightning shielding failure
Author
Nayel, Mohamed ; Jie, Zhao ; He, Jinliang
Author_Institution
Xi´´an Jiaotong Liverpool Univ., Xi´´an, China
fYear
2011
fDate
1-4 Nov. 2011
Firstpage
144
Lastpage
149
Abstract
This paper proposes a modification to the electrogeometric model. By using Eriksson equation multiplied by a proposed voltage coefficient, electrogeometric models of an unshielded horizontal conductor and a shielded conductor are constructed to study the lightning striking rates at different heights, lightning current and when it is stressed by AC and DC voltages. The shielding failure rates of 500 kV AC and DC flat transmission lines are studied and discussed for different shielding angles, voltage phase angles. The shielding failure rates of 500 kV AC and DC flat transmission lines results are compared with those neglecting transmission line voltages as studied before.
Keywords
DC transmission networks; conductors (electric); lightning protection; shielding; Eriksson equation; ac flat transmission lines; dc flat transmission lines; electrogeometric model; electrogeometric models; lightning shielding failure; shielding failure rates; unshielded horizontal conductor; voltage 500 kV; Conductors; Equations; Lightning; Mathematical model; Poles and towers; Power transmission lines; Wires; Conductor voltage; Electrogeometric model; Lightning; Shielding failure; Transmission line;
fLanguage
English
Publisher
ieee
Conference_Titel
Lightning (APL), 2011 7th Asia-Pacific International Conference on
Conference_Location
Chengdu
Print_ISBN
978-1-4577-1467-2
Type
conf
DOI
10.1109/APL.2011.6111091
Filename
6111091
Link To Document