DocumentCode
2758307
Title
Operation assessment of an installed ±75 kVAr STATCOM
Author
Eskandari, M.D. ; Bina, Nf Tavakoli ; Panahlou, M.A.
Author_Institution
ACECR Nasir Branch Res. Center, Tehran, Iran
Volume
1
fYear
2003
fDate
17-20 Nov. 2003
Firstpage
167
Abstract
A static compensator (STATCOM) is a FACTS controller, which can either absorb or deliver reactive power to power systems. A ±75 kVAr STATCOM was installed for a substation in Tehran distribution system. This work demonstrates operation of an installed STATCOM while the imbalance of the substation on the STATCOM behaviour is considered. Different practical results show the quick variations of the capacitor voltage. This is due to an energy oscillation at twice the synchronous frequency between the dc and ac sides. This oscillation also introduces low order harmonics to the inverter output voltages and currents, causing distortion of waveforms along with a poor performance for STATCOM.
Keywords
compensation; flexible AC transmission systems; harmonic distortion; power transmission control; substations; 75 kVAr; FACTS controller; STATCOM; Tehran distribution system; capacitor voltage; energy oscillation; inverter output voltages; low order harmonics; power systems; reactive power; static compensator; substation; synchronous frequency; waveform distortion; Automatic voltage control; Capacitors; Control systems; Frequency; Inverters; Power system harmonics; Power systems; Reactive power control; STATCOM; Substations;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics and Drive Systems, 2003. PEDS 2003. The Fifth International Conference on
Print_ISBN
0-7803-7885-7
Type
conf
DOI
10.1109/PEDS.2003.1282744
Filename
1282744
Link To Document