DocumentCode
2758365
Title
Experimental studies of breakdown characteristics of a 12-kV arcing horn under a lightning impulse superimposed on AC voltage
Author
Arnacha, Sunchai ; Kunakorn, Anantawat ; Yutthagowith, Peerawut ; Tuethong, Piyapon
Author_Institution
Electr. Eng. Dept., King Mongkut´´s Inst. of Technol. Ladkrabang, Bangkok, Thailand
fYear
2011
fDate
1-4 Nov. 2011
Firstpage
205
Lastpage
208
Abstract
This paper presents the studies of breakdown characteristics of a 12-kVarcing horn under a lighting impulse superimposed on an AC power frequency voltage at various angles. The lightning impulse is superimposed on the AC power frequency voltage at a phase angle varied from 0° to 360. The 12-kV arcing horn under test has dimension and configuration according to DIN 42531 standard. The critical breakdown voltages (Ub50%) with and without superposition of an impulse voltage on the AC voltage are investigated and made comparison. It is found that the statistical breakdown voltages are depended on the phase angle of the AC voltage superposed by the lightning impulse voltage. From the test results, the AC voltage affects the insulation level and it should be taken into account in an insulation design and insulation coordination.
Keywords
arcs (electric); electric breakdown; lightning protection; AC power frequency voltage; DIN 42531 standard; arcing horn; breakdown characteristics; impulse voltage; insulation coordination; insulation design; insulation level; lightning impulse; statistical breakdown voltages; voltage 12 kV; Breakdown voltage; Insulation; Lightning; Low pass filters; Power transformer insulation; Voltage control; Voltage measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Lightning (APL), 2011 7th Asia-Pacific International Conference on
Conference_Location
Chengdu
Print_ISBN
978-1-4577-1467-2
Type
conf
DOI
10.1109/APL.2011.6111104
Filename
6111104