• DocumentCode
    2758561
  • Title

    Added critical flashover voltage by fiberglass crossarm to 15 kV polymer suspension insulator

  • Author

    Grzybowski, S. ; Talabathula, S. ; Ward, R.

  • Author_Institution
    Dept. of Electr. & Comput. Eng, Mississippi State Univ., Starkville, MS, USA
  • fYear
    2012
  • fDate
    10-13 June 2012
  • Firstpage
    404
  • Lastpage
    408
  • Abstract
    The paper is based on the investigative studies performed on the fiberglass crossarm which will be generally used in the distribution line structures as an additional insulation component. Lightning impulse voltage tests were conducted on the fiberglass crossarm alone to determine its critical flashover (CFO) voltage, and also the critical flashover voltage of 15 kV polymer suspension insulator plus the fiberglass crossarm. The added CFO voltage of the fiberglass crossarm to the insulator was determined with polymer suspension insulator as the primary insulation component and the fiberglass crossarm as the secondary insulation component. The added CFO voltage was evaluated for 1 ft through 5 ft length of the fiberglass crossarm for both positive and negative polarity, under dry and wet condition. All these tests were conducted in the High Voltage Laboratory at Mississippi State University. A comparison of the CFO and added CFO voltages by the fiberglass crossarm to the polymer suspension insulator with the CFO and added CFO voltages of wood crossarm to the polymer suspension insulator is presented.
  • Keywords
    flashover; glass fibres; impulse testing; polymer insulators; power distribution lines; CFO voltage; Mississippi State University; critical flashover voltage; distribution line structures; fiberglass crossarm; high-voltage laboratory; insulation component; lightning impulse voltage tests; polymer suspension insulator; voltage 15 kV; wood crossarm; Flashover; Insulators; Lightning; Optical fiber testing; Polymers; Suspensions; added critical flashover voltage; additional insulation component; basic insulation level (BIL); critical flashover (CFO) voltage; electrical strength; fiberglass crossarm; flashover; insulation; overvoltages;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation (ISEI), Conference Record of the 2012 IEEE International Symposium on
  • Conference_Location
    San Juan, PR
  • ISSN
    1089-084X
  • Print_ISBN
    978-1-4673-0488-7
  • Electronic_ISBN
    1089-084X
  • Type

    conf

  • DOI
    10.1109/ELINSL.2012.6251499
  • Filename
    6251499