  • Abstract
    An algorithm has been developed to predict the remaining available battery capacity when a power outage occurs in telecommunication power supplies. This algorithm was formulated based on electrochemical phenomena during discharge. The effects of surface area, voltage, acid concentration and temperature on capacity were also included. An evaluation of the algorithm was performed using a variety of batteries, both flooded and valve-regulated. The results showed good accuracy in predicting the remaining capacity. In application, the algorithm is part of a plant controller that monitors voltage, current and temperature of the batteries. State-of-charge data is calculated when a discharge is detected
  • Keywords
    electrochemistry; lead; secondary cells; telecommunication power supplies; uninterruptible power supplies; Pb; Pb-acid secondary batteries; acid concentration; discharge; electrochemical phenomena; flooded batteries; power outage; remaining capacity estimation; reserve time prediction algorithm; state-of-charge data; surface area; telecommunication UPS; temperature; valve-regulated batteries; voltage; Batteries; Current density; Electrodes; Laboratories; Prediction algorithms; Surface discharges; Surface resistance; Temperature; Testing; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 1996. INTELEC '96., 18th International
  • Conference_Location
    Boston, MA
  • Print_ISBN
    0-7803-3507-4
  • Type

    conf

  • DOI
    10.1109/INTLEC.1996.573400
  • Filename
    573400