A new method for avoiding overvoltages when clearing DC-line faults with a low SCR HVDC station
Author
Joetten, R. ; Zong, Y.
Author_Institution
TH Darmstadt, Germany
fYear
1991
fDate
17-20 Sep 1991
Firstpage
401
Lastpage
403
Abstract
Two promising variants for avoiding AC-side overvoltages at DC, line faults of low-SCT (short-circuit ratio) HVDC systems have been presented. Both use commutation switches. The first one has moderate demands on the mechanical speed of the switches, but requires further investigation on the arc extinction. The second one uses the converters to extinguish the arc, requires almost no commutation duty by the switches, but does demand fast acting switches (20-30 ms). The residual current references to be set at a monopolar fault in a bipolar system must be carefully precalculated and tested dynamically at the simulator. The authors conclude that only the current of the faulty pole should be manipulated. It is based on a comparison by a simple calculation
Keywords
DC power transmission; commutation; digital simulation; electrical faults; power engineering computing; substations; switches; DC line faults clearance; HVDC station; arc extinction; bipolar system; commutation switches; fast acting switches; faulty pole; low short-circuit ratio; mechanical speed; monopolar fault; overvoltage avoidance; residual current;