DocumentCode
2763920
Title
Leakage current monitoring of insulators exposed to marine and industrial pollution
Author
Kanashiro, Arnaldo G. ; Burani, Geraldo F.
Author_Institution
Inst. of Electrotech. & Energy, Sao Paulo Univ., Brazil
Volume
1
fYear
1996
fDate
16-19 Jun 1996
Firstpage
271
Abstract
This paper presents the results of a research project considering 13.8 kV distribution line and 88 kV transmission line insulators, exposed to marine and industrial pollution, respectively. Leakage current measurements were performed in the field. Tests were performed in the laboratory and registration instruments were developed to enable measurements of the leakage current values in the field and at the laboratory. Various correlations were performed with the measurements of: leakage current; climatic conditions; and the amount of the pollutants on the insulators surface. Suitable insulators were selected for distribution lines and permissible levels of the leakage current were analyzed for transmission lines
Keywords
distribution networks; electric breakdown; electric current measurement; insulator contamination; insulator testing; leakage currents; power transmission lines; 13.8 kV; 88 kV; climatic conditions; distribution line; industrial pollution; insulator leakage current monitoring; insulator surface pollutants; leakage current measurements; marine pollution; research project; transmission line; Current measurement; Industrial pollution; Insulation; Laboratories; Leakage current; Monitoring; Performance evaluation; Pollution measurement; Testing; Transmission line measurements;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation, 1996., Conference Record of the 1996 IEEE International Symposium on
Conference_Location
Montreal, Que.
ISSN
1089-084X
Print_ISBN
0-7803-3531-7
Type
conf
DOI
10.1109/ELINSL.1996.549334
Filename
549334