DocumentCode :
2766981
Title :
A second look at generator 51 V relays
Author :
Ventruella, D.J. ; Steciuk, Pete
Author_Institution :
GE, Birmingham, AL, USA
fYear :
1996
fDate :
10-14 June 1996
Firstpage :
209
Lastpage :
219
Abstract :
ANSI/IEEE device type 51 V relays have long been used as back-up overcurrent protection for industrial generators. Many systems have experienced a steady increase in size since the introduction of the ANSI/IEEE device type 51 V voltage restrained overcurrent relay. This growth has resulted in the need for several levels of coordination timing delay between phase overcurrent relays and has seen the introduction of tie circuits (synchronizing reactor buses, tie circuit breakers, etc.) in some cases rated for ampacities greater than that of one or more of the generators present. The settings required for certain ANSI/IEEE device type 51 V relays, in order to coordinate on a standard basis with other phase overcurrent relays in the power system, may result in large time delays and/or high trip current levels. This could make for a severe compromise between protection and selectivity. An auxiliary, or alternative device to use in conjunction with the ANSI/IEEE device type 51 V voltage restrained relay in some cases may be an inverse characteristic undervoltage relay. The need for such a device will be influenced by the exciter type present on a specific generator, the number of levels of phase overcurrent relay coordination in the system, and the philosophy of the individual engineer with regard to the issue of compromising between protection and coordination.
Keywords :
ANSI standards; IEEE standards; electric generators; machine protection; overcurrent protection; power system protection; power system relaying; relay protection; 15 kV; ANSI/IEEE device type 51 V relays; ampacities; back-up overcurrent protection; coordination timing delay; industrial generators; inverse characteristic undervoltage relay; overcurrent relay coordination; phase overcurrent relays; ratings; synchronizing reactor buses; tie circuit breakers; tie circuits; voltage restrained overcurrent relay; ANSI standards; Circuit breakers; Delay; Inductors; Power system protection; Power system relaying; Protective relaying; Relays; Timing; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Pulp and Paper Industry Technical Conference, 1996., Conference Record of 1996 Annual
Conference_Location :
Birmingham, AL, USA
ISSN :
0190-2172
Print_ISBN :
0-7803-3148-6
Type :
conf
DOI :
10.1109/PAPCON.1996.536000
Filename :
536000