DocumentCode :
2777735
Title :
Electrical breakdown strength of 5 kV XLPE cable with imperfections under combined AC-DC voltage
Author :
Grzybowski, S. ; Fan, J.
Author_Institution :
Dept. of Electr. & Comput. Eng., Mississippi State Univ., MS, USA
Volume :
2
fYear :
1996
fDate :
16-19 Jun 1996
Firstpage :
616
Abstract :
This paper presents data on electrical breakdown strength of 5 kV XLPE cable with imperfection under AC voltage, DC voltage and superimposed AC upon DC voltage (pulsate voltage). In the later case, the measurement was taken over a wide range of pulsate ratio, which is defined as p=Vac/Vdc. Comparison with the former measurement results for sound cables shows that the pulsate voltage can be used to detect the imperfections inside XLPE cable. Based on past research, the results obtained under combined AC plus DC voltage follow an expression which relates the breakdown voltage to the sum of the arctangent and arccotangent function of the parameter “p”
Keywords :
XLPE insulation; electric breakdown; electric strength; impulse testing; insulation testing; power cable insulation; 5 kV; AC voltage; DC voltage; XLPE cable; arccotangent function; arctangent function; cable imperfections detection; electrical breakdown strength; pulsate voltage; superimposed AC upon DC voltage; Breakdown voltage; Cable insulation; Electric breakdown; Flashover; Laboratories; Oil insulation; Power cable insulation; Power cables; Power transformer insulation; Testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 1996., Conference Record of the 1996 IEEE International Symposium on
Conference_Location :
Montreal, Que.
ISSN :
1089-084X
Print_ISBN :
0-7803-3531-7
Type :
conf
DOI :
10.1109/ELINSL.1996.549421
Filename :
549421
Link To Document :
بازگشت