• DocumentCode
    2778190
  • Title

    A comparison of analytical and conventional techniques for thermal endurance characterization of cable insulation

  • Author

    Motori, A. ; Montanari, G.C. ; Centurioni, L. ; Coletti, G.

  • Author_Institution
    Bologna Univ., Italy
  • Volume
    2
  • fYear
    1996
  • fDate
    16-19 Jun 1996
  • Firstpage
    632
  • Abstract
    The thermal endurance characterization of ethylene-propylene rubber (EPR) insulated cables for medium voltage applications is performed by both conventional long-term life tests and resorting to an analytical technique, which is based on measurements of the oxidative stability of the insulation. It is shown that the temperature index and the halving interval provided by the two methods are very close. Comparisons are finally made with the results previously obtained applying the same procedures to high voltage EPR cables
  • Keywords
    ethylene-propylene rubber; EPR insulated cables; cable insulation; ethylene-propylene rubber; halving interval; long-term life tests; medium voltage applications; oxidative stability; temperature index; thermal endurance characterization; Cable insulation; Cables; Insulation testing; Life testing; Medium voltage; Paramagnetic resonance; Performance analysis; Performance evaluation; Rubber; Stability analysis;