• DocumentCode
    278218
  • Title

    Dielectric performance of gas-insulated switchgear and possible methods of on-line monitoring

  • Author

    Pryor, B.M.

  • fYear
    1991
  • fDate
    33322
  • Firstpage
    42491
  • Lastpage
    42492
  • Abstract
    The dielectric performance of gas-insulated switchgear (GIS) is critical to its long term service integrity. Many parameters that are of little significance to open type air insulated switchgear are of vital importance to GIS. Detailed on-site examination is necessary to ensure chamber cleanliness during site erection as a foreign object left inside can in itself induce dielectric breakdown. In addition loose, or ineffectively bonded, line or earth side components can vibrate under the effects of both magnetic and electrostatic forces to induce partial discharge activity
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Insulation Diagnostics - Methods for Determining Quality, Remnant Life and Proof Testing, IEE Colloquium on
  • Conference_Location
    London
  • Type

    conf

  • Filename