DocumentCode
278218
Title
Dielectric performance of gas-insulated switchgear and possible methods of on-line monitoring
Author
Pryor, B.M.
fYear
1991
fDate
33322
Firstpage
42491
Lastpage
42492
Abstract
The dielectric performance of gas-insulated switchgear (GIS) is critical to its long term service integrity. Many parameters that are of little significance to open type air insulated switchgear are of vital importance to GIS. Detailed on-site examination is necessary to ensure chamber cleanliness during site erection as a foreign object left inside can in itself induce dielectric breakdown. In addition loose, or ineffectively bonded, line or earth side components can vibrate under the effects of both magnetic and electrostatic forces to induce partial discharge activity