DocumentCode
2782350
Title
Prebreakdown and breakdown phenomena in large oil gaps under AC
Author
Saker, A. ; Gournay, P. ; Trinh, N. Giao ; Boisdon, C. ; Lesain, O. ; Tobazéon, R.
Author_Institution
Lab. d´´Electrostat. et de Mater. Dielectr., CNRS, Grenoble, France
Volume
2
fYear
1996
fDate
16-19 Jun 1996
Firstpage
733
Abstract
This paper presents a study of prebreakdown and breakdown phenomena under AC voltage in mineral oil in large gaps to 60 cm. The investigations presented concern the study of streamers and the measurement of breakdown voltages in rod-plane and sphere-plane gaps. Also, the influence of a contamination by solid particles in the oil has been considered. A specific breakdown mode under AC voltage is evidenced, where “bursts” of streamers lead to the lowest breakdown fields recorded. Numerical values of the mean field in oil required for “direct” or “burst” breakdown modes are derived from the experiments. As a consequence, the great sensitivity to the presence of particles of EHV transformers insulation with large oil gaps is pointed out
Keywords
electric breakdown; insulation testing; power transformer insulation; power transformer testing; power transformers; transformer oil; voltage measurement; AC voltage; EHV transformers insulation; breakdown phenomena; breakdown voltage measurements; direct breakdown; large gaps; mineral oil; prebreakdown phenomena; rod-plane gaps; solid particles contamination; sphere-plane gap; streamer burst breakdown; streamer inception frequency; Breakdown voltage; Electric breakdown; Electrodes; Insulators; Minerals; Petroleum; Pollution measurement; Testing; Transformers; Wire;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation, 1996., Conference Record of the 1996 IEEE International Symposium on
Conference_Location
Montreal, Que.
ISSN
1089-084X
Print_ISBN
0-7803-3531-7
Type
conf
DOI
10.1109/ELINSL.1996.549449