Title
Registration experience of partial discharges in operating equipment with digital oscillograph
Author
Golenko, O.V. ; Zhivodernikov, S.V. ; Ovsyannikov, A.G.
Author_Institution
Siberian Res. Inst. of Power Eng.
fYear
2000
fDate
2000
Firstpage
39
Lastpage
41
Abstract
The paper discusses the measurement of partial discharges from AT-2 autotransformers, and also AT-3 and AT-4 groups, using digital oscillographs. The techniques of registration of PD differed for different objects according to available capabilities. For AT-2 the measured signals on CP of inputs of one class of voltage but different phases, and also signals on CP of inputs 220 and 110 kV of one phase were investigated. Thus the filtration of signals by series connection to circuit of high frequencies filters, and coordination of impedance of a cable with load was performed. During registration polarity and level of start of sweep, the scales on axes of the oscillograms changed. Finally the distinctive features of signals of a different kind of interference including corona, and PD were determined
Keywords
autotransformers; digital instrumentation; oscillographs; partial discharge measurement; signal processing; 110 kV; 220 kV; AT-2 autotransformers; cable impedance/load coordination; corona; digital oscillograph; high frequencies filters; interference; operating equipment; partial discharges measurement; polarity; series connection; signals filtering; Circuits; Corona; Filters; Filtration; Frequency; Impedance; Interference; Partial discharges; Phase measurement; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Modern Techniques and Technology, 2000. MTT 2000. Proceedings of the VI International Scientific and Practical Conference of Students, Post-graduates and Young Scientists
Conference_Location
Tomsk
Print_ISBN
0-7803-5789-2
Type
conf
DOI
10.1109/SPCMTT.2000.896035
Filename
896035
Link To Document