• DocumentCode
    2789111
  • Title

    New principle of transformer protection based on spectral entropy characteristics

  • Author

    Feifei, Zhou ; Yan, Xu

  • Author_Institution
    Sch. of Electr. & Electron. Eng., North China Electr. Power Univ., Baoding, China
  • fYear
    2010
  • fDate
    20-22 Sept. 2010
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    A new transformer protection theory based on spectral entropy characteristics is put forward in this paper. First, the algorithm of empirical mode decomposition (EMD) and entropy are developed, and variation trends of spectral entropy characteristics are analyzed in the case of inrush currents and internal fault currents. EMD algorithm is used to conduct the accurate location of current breaks and the spectral entropy is calculated for all of the states. The advantages of the method are little computation, reliable and quick operation. The results of dynamic analog testing confirmed that the method is able to clear the internal fault reliably and quickly. Moreover, compared with the second harmonic restraint principle, the proposed algorithm has better performance.
  • Keywords
    circuit breakers; entropy; fault currents; power transformer protection; EMD; current breakers; empirical mode decomposition; inrush currents; internal fault currents; spectral entropy characteristics; transformer protection; Circuit faults; Current transformers; Entropy; Surge protection; Surges; Switches; EMD; inrush current; power transformer; spectral entropy;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Critical Infrastructure (CRIS), 2010 5th International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    978-1-4244-8080-7
  • Type

    conf

  • DOI
    10.1109/CRIS.2010.5617482
  • Filename
    5617482