Title :
Study on method of single-phase-to-earth fault section location in neutral point resonant grounded system
Author :
Zheng, Qi ; Zhao, Zheng ; Yihan, Yang
Author_Institution :
North China Electr. Power Univ., Beijing, China
Abstract :
Due to the large amount of branches and high grounding resistance of the distribution network, the earth fault location has not been solved effectively. A live location method is proposed for the single-phase-to-earth fault section in the neutral point resonant grounded system. By this method, the compensation current of arc-suppression coil is adjusted after the metallic earth fault occurs. And the fault section can be confirmed by the variation of zero-sequence current measured by FTU equipped in the lines, for the zero-sequence current in the non-fault path is proportional to the zero-sequence voltage. When the single-phase-to-earth fault via resistance occurs, zero-sequence voltage changes after the arc-suppression coil is adjusted. The method is also effective as long as the zero-sequence current is converted by zero-sequence voltage. The site experiments have been carried out to prove that the method is feasible.
Keywords :
arcs (electric); earthing; fault location; power distribution faults; power distribution protection; arc-suppression coil; compensation current; distribution network; grounding resistance; live location method; metallic earth fault; neutral point resonant grounded system; single-phase-to-earth fault section location; zero-sequence current; zero-sequence voltage; Automation; Circuit faults; Coils; Earth; Fault location; Inductance; Power systems; arc-suppression coil; fault section location; neutral point resonant grounded system; single-phase-to-earth fault;
Conference_Titel :
Critical Infrastructure (CRIS), 2010 5th International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-8080-7
DOI :
10.1109/CRIS.2010.5617537