    Influence of the non-uniformity of pollution distribution on the electrical behavior of insulators

  • Author

    Garcia, Ricardo W S ; Bosignoli, Ronaldo ; Gomes, Edegard, Jr.

  • Author_Institution
    Centro de Pesquisas de Energia Eletrica, Rio de Janeiro, Brazil
  • fYear
    1991
  • fDate
    8-12 Jul 1991
  • Firstpage
    342
  • Abstract
    Presents an analysis of the influence of pollution distribution on insulator surfaces, considering service conditions. The main subjects considered are the utilization of equivalent salt deposit density (ESDD) to measure site severities and the simulation of natural pollution distribution by artificial pollution test methods to represent it in the laboratory. Results show that special care must be taken when average SDD values are considered. The conclusions lead to a better representation of service conditions when the electrical behavior of polluted insulators is evaluated by artificial pollution methods at laboratories, regarding the influence of pollution concentration
  • Keywords
    air pollution; insulation testing; insulators; artificial pollution test methods; electrical behavior; equivalent salt deposit density; insulators; pollution concentration; pollution distribution; service conditions; Circuit testing; Dielectrics and electrical insulation; Environmentally friendly manufacturing techniques; Flashover; Insulator testing; Laboratories; Pollution measurement; Power transformer insulation; Surface contamination; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Properties and Applications of Dielectric Materials, 1991., Proceedings of the 3rd International Conference on
  • Conference_Location
    Tokyo
  • Print_ISBN
    0-87942-568-7
  • Type

    conf

  • DOI
    10.1109/ICPADM.1991.172068
  • Filename
    172068