Abstract :
Compressed SF6 gas is the main high-voltage insulation medium in gas insulated equipment. Recent progress in studies of high-voltage breakdown in uniform, quasi-uniform, and nonuniform field systems is described. This includes time lags to breakdown, the effect of particle contamination, and the flashover of insulators. Significant progress has been made in developing models for calculating the breakdown voltage in uniform fields. Nonuniform field streamer and leader models have also been developed and have been applied to particle initiated breakdown. Recommendations are given for future work to clarify the mechanisms and critical parameters, particularly for the flashover of insulators
Keywords :
electric breakdown of gases; flashover; gaseous insulation; insulators; sulphur compounds; SF6; flashover; gas insulated equipment; high voltage gas breakdown; high-voltage insulation medium; insulators; leader models; nonuniform field systems; particle contamination; particle initiated breakdown; quasi-uniform field; streamer models; time lags; uniform field; Breakdown voltage; Dielectric breakdown; Dielectrics and electrical insulation; Electric breakdown; Electrodes; Flashover; Gas insulation; Gases; Plastic insulation; Sulfur hexafluoride;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Properties and Applications of Dielectric Materials, 1991., Proceedings of the 3rd International Conference on
Conference_Location :
Tokyo
Print_ISBN :
0-87942-568-7
Type :
conf
DOI :
10.1109/ICPADM.1991.172075
Filename :
172075
Link To Document :
بازگشت