• DocumentCode
    2794811
  • Title

    Study on diagnostic method of deterioration for power capacitors

  • Author

    Yorozuya, T. ; Takasu, N. ; Suganuma, K. ; Takahashi, K. ; Kamba, K. ; Ichiwara, T.

  • Author_Institution
    Tokyo Electric Power Co., Japan
  • fYear
    1991
  • fDate
    8-12 Jul 1991
  • Firstpage
    745
  • Abstract
    For oil-impregnated type capacitors, thermal and electrical accelerating deterioration tests were conducted to study their various characteristics until their dielectric breakdown occurred. A diagnosis method for the deterioration analysis of gases dissolved in oil was also studied. CO+CO2 gas is shown to be an effective index for the thermal deterioration. Since C2H2 is generated only by the partial discharge, it is possible to estimate the occurrence of partial discharge. While capacitors are deteriorated by thermal stress, it is considered that the dielectric strength of the insulating oil decreases due to gases dissolved in oil
  • Keywords
    ageing; electric breakdown of liquids; insulating oils; partial discharges; power capacitors; deterioration; diagnostic method; dielectric breakdown; dielectric strength; oil-impregnated type; partial discharge; power capacitors; thermal deterioration; Dielectric breakdown; Dissolved gas analysis; Gases; Life estimation; Partial discharges; Petroleum; Power capacitors; Testing; Thermal conductivity; Thermal stresses;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Properties and Applications of Dielectric Materials, 1991., Proceedings of the 3rd International Conference on
  • Conference_Location
    Tokyo
  • Print_ISBN
    0-87942-568-7
  • Type

    conf

  • DOI
    10.1109/ICPADM.1991.172173
  • Filename
    172173