DocumentCode :
2795438
Title :
Application of gate-controlled series capacitors (GCSC) for reducing stresses due to sub-synchronous resonance in turbine-generator shaft
Author :
Umre, B.S. ; Helonde, J.B. ; Modak, J.P. ; Renkey, S.
Author_Institution :
Visvesvaraya Nat. Inst. of Technol., Nagpur, India
fYear :
2010
fDate :
12-16 Sept. 2010
Firstpage :
2300
Lastpage :
2305
Abstract :
The main purpose of this paper is to verify the capability of the gate controlled series capacitor (GCSC) to mitigate subsynchronous resonance (SSR) and electromechanical oscillations that occur when a steam turbine-generator (T-G) is connected to a long transmission line with series compensation. SSR develops the stresses at the coupling of T-G set. This investigation was done based on the IEEE First Benchmark Model. Turn-off pulse generator with zero crossing detectors is used for GCSC. By using turn-off pulse generator capacitive reactance of transmission line can be controlled and hence SSR is mitigated. The Matlab simulink is employed to simulate the effect on stresses of T-G shaft. The simulations results show how the stresses on T-G shaft reduce with the application of GCSC.
Keywords :
pulse generators; steam turbines; subsynchronous resonance; turbogenerators; electromechanical oscillation; gate controlled series capacitor; steam turbine generator; subsynchronous resonance; transmission line; turn off pulse generator; zero crossing detector; Capacitors; Generators; IP networks; Mathematical model; Shafts; Stress; Torque; Capacitor compensated transmission lines; power generation mechanical factors; power system dynamic stability; power system modeling; subsynchronous resonance; thyristor applications; turbo generators;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Energy Conversion Congress and Exposition (ECCE), 2010 IEEE
Conference_Location :
Atlanta, GA
Print_ISBN :
978-1-4244-5286-6
Electronic_ISBN :
978-1-4244-5287-3
Type :
conf
DOI :
10.1109/ECCE.2010.5617863
Filename :
5617863
Link To Document :