• DocumentCode
    2797387
  • Title

    Electric strength of insulating caps between transformer winding taps and structure elements

  • Author

    Antonov, V.I. ; Danishina, A.A. ; Morozova, T.I.

  • Author_Institution
    All-Union Electrotech. Inst., Moscow, USSR
  • fYear
    1991
  • fDate
    8-12 Jul 1991
  • Firstpage
    1274
  • Abstract
    It is experimentally shown that the electric strength of an insulated tap-plane insulation structure is influenced by the field stress appearing in the oil on the tap solid insulation surface and by the stressed oil volume bounded by an 80% equigradient surface. An analytical formula was obtained for the relationship between the stressed oil volume and the field stress at which a partial discharge of sufficiently high intensity starts in the oil-filled gap. The technique of estimating the electric strength, developed by using this formula, allowed the tap-plane insulation gap length to be decreased by 25-30% without reducing the insulation reliability
  • Keywords
    electric strength; insulating oils; insulation testing; partial discharges; transformer insulation; electric strength; equigradient surface; field stress; insulating caps; insulation reliability; oil-filled gap; partial discharge; stressed oil volume; structure elements; tap-plane insulation structure; transformer winding taps; Circuits; Dielectric breakdown; Dielectrics and electrical insulation; Oil insulation; Partial discharges; Petroleum; Power transformer insulation; Proposals; Stress; Windings;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Properties and Applications of Dielectric Materials, 1991., Proceedings of the 3rd International Conference on
  • Conference_Location
    Tokyo
  • Print_ISBN
    0-87942-568-7
  • Type

    conf

  • DOI
    10.1109/ICPADM.1991.172313
  • Filename
    172313