• DocumentCode
    2797842
  • Title

    Fault isolation within power distribution systems

  • Author

    Lee, Ellen S. ; Herbert, Alexander S., Jr.

  • Author_Institution
    AT&T Bell Lab., Mesquite, TX, USA
  • fYear
    1991
  • fDate
    5-8 Nov 1991
  • Firstpage
    74
  • Lastpage
    79
  • Abstract
    Faults originating in one equipment group may be coupled into other equipment groups. A coupling mechanism appears as impedances in the power distribution system which are common to several equipment groups. The authors demonstrate that the effect of these impedances can be controlled using local energy sources. A detailed lumped-constant model of a typical telecommunications power distribution system and a SPICE-based computer analysis are used to estimate the short-circuit induced voltage transients. In addition, results from a laboratory model of the system are used to validate the computer model and provide additional insights into the problem. The authors conclude that fuse operating time is not a critical parameter in the design of fault tolerant systems
  • Keywords
    distribution networks; electrical faults; power engineering computing; telecommunication systems; transients; SPICE-based computer analysis; fault isolation; fault tolerant systems; fuse operating time; lumped-constant model; power distribution systems; short-circuit induced voltage transients; telecommunications; Distributed computing; Fault tolerant systems; Fuses; Impedance; Power distribution; Power system modeling; Telecommunication computing; Telecommunication control; Transient analysis; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 1991. INTELEC '91., 13th International
  • Conference_Location
    Kyoto
  • Print_ISBN
    0-87942-670-5
  • Type

    conf

  • DOI
    10.1109/INTLEC.1991.172376
  • Filename
    172376