Title :
Corrected harmonic loss factor for transformers supplying nonsinusoidal load currents
Author :
Makarov, Sergey N. ; Emanuel, Alexander E.
Author_Institution :
Worcester Polytech. Inst., MA, USA
Volume :
1
fYear :
2000
fDate :
2000
Firstpage :
87
Abstract :
The assumption that the eddy-current losses in transformer windings is proportional with the square of the frequency is reasonable when conductors with sides less than 3 mm are used. For conductors with larger dimensions, such assumption leads to conservative results. This paper provides a corrected harmonic loss factor that leads to more accurate prediction of transformer capability to operate when supplying nonsinusoidal load currents
Keywords :
eddy current losses; harmonic distortion; power supply quality; power system harmonics; power transformers; transformer windings; corrected harmonic loss factor; eddy-current losses; nonsinusoidal load currents supply; power quality; power transformer windings; transformer capability prediction; Conductors; Current supplies; Eddy currents; Electrical equipment industry; Frequency; Hafnium; Magnetic fields; Power system harmonics; Transformers; USA Councils;