• DocumentCode
    2798558
  • Title

    A study of heat recovery from fuel cell exhaust gas for telecommunications equipment cooling

  • Author

    Oshima, Kazuo ; Uekusa, Tsuneo ; Ichimura, Masahiro ; Koyashiki, Tohru

  • Author_Institution
    NTT Corp., Tokyo, Japan
  • fYear
    1991
  • fDate
    5-8 Nov 1991
  • Firstpage
    379
  • Lastpage
    386
  • Abstract
    Heat recovery methods and the amount of heat that can be recovered from fuel cell exhaust gas are described. The cooling performance of an absorption refrigerator that uses fuel cell waste heat is also described. Two heat recovery methods from the exhaust gas are considered. One uses heat recovery from mixed exhaust gas from the cathode side of the cells and the reformer (mixed type); the other uses separate heat recovery from these sites (separate type). Simulation shows that the amount of heat recovered between 60 and 75°C with the separate type of heat recovery is greater than with the mixed type of heat recovery. The cooling capacity of the refrigerator using the separate type of heat recovery and recovering heat between 65 and 85°C is about 2.5 times that of one using a generator (heat source) with a constant 85°C temperature
  • Keywords
    cooling; fuel cells; refrigeration; refrigerators; telecommunication equipment; 60 to 75 degC; 65 to 85 degC; absorption refrigerator; cathode; cooling; fuel cell exhaust gas; heat recovery; performance; telecommunications equipment; Absorption; Cathodes; Communication switching; Cooling; Fuel cells; Heat recovery; Refrigeration; Space heating; Waste heat; Water heating;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 1991. INTELEC '91., 13th International
  • Conference_Location
    Kyoto
  • Print_ISBN
    0-87942-670-5
  • Type

    conf

  • DOI
    10.1109/INTLEC.1991.172424
  • Filename